Model | HSCP-2K4-9 | HSCP-2K4-12 | HSCP-2K4-15 | HSCP-2K4-18 | HSCP-2K4-24 | HSCP-2K4-36 | HSCP-2K4-48 | HSCP-2K4-60 |
Output | DC voltage | 9V | 12V | 15V | 18V | 24V | 36V | 48V | 60V |
Voltage tolerance | +/-2% | +/-1% | +/-1% | +/-1% | +/-1% | +/-1% | +/-1% | +/-1% |
Rated current | 266A | 200A | 160A | 133A | 100A | 66A | 50A | 40A |
Current range | 0-266A | 0-200A | 0-160A | 0-133A | 0-100A | 0-66A | 0-50A | 0-40A |
Rated power | 2400W | 2400W | 2400W | 2400W | 2400W | 2400W | 2400W | 2400W |
Ripple & noise | 90mVp-p | 120mVp-p | 150mVp-p | 150mVp-p | 150mVp-p | 200mVp-p | 200mVp-p | 200mVp-p |
DC voltage adj. range | Can adjust from 20%-100% output voltage by external control 1-5V |
Setup, rise, hold time | 800ms 400ms 12ms at full load |
Input | Voltage range | 180~260VAC 3Φ4 47~63Hz |
AC current | 15A/230VAC |
Efficiency | 83% | 84% | 85% | 86% | 88% | 88% | 89% | 89% |
Inrush current | 60A/230V |
Leakage current | 3.5Ma/240VDC |
Protection | Over load | 110~140% |
Protection type: current limiting, delay shut down o/p voltage, re-power on to recover |
Over voltage | 110~135% |
Protection type: shut down o/p voltage, re-power on to recover |
Over temperature | TSW1(Power transistor) Temp>100ºC Shut down o/p voltage, temp.<100ºC, O/I auto recovery |
Environment | Working temp. & humidity | -10ºC~+65ºC, 20%~90%RH |
Storage temp. & Humidity | -10ºC~+85ºC, 20%~95%RH |
Vibration | 10~200Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes |
Safety | Withstand voltage | I/P-O/P: 3KVAC I/P-FG:>1.5KVAC O/P-FG:0.5KVAC |
Isolation resistance | I/P-O/P-FG:>100MΩ/500VDC |
Standards | Safety standards | Design refer to UL1950, CSA22.2, IEC60950 |
EMC standards | Design refer to FCC Part 15 Class A |
Others | Weight | 9kg |
Packing | 1pcs/10kg/carton |